Online UPS 3 Phase O/P-CP3315L20

Key Features & Application
- True Online double conversion design
- Output isolation transformer.
- Wide Input voltage range
- User -friendly digital LCD display
- Cold start function
- High crest factor circuit design
- Advanced Battery Management
- Improved input power factor
Model: CP3315L20
|
|
Feature | CP3315L20 |
Input | |
Voltage range(VAC) | 320-480Vac @ 100% Load ,Three Phase (4 wire). |
Frequency range (Hz) | 50Hz±10%. |
Power Factor | >0.95 |
Output | |
Power (VA) | 15000 |
Power Factor | 0.8(Standard) |
Voltage(V) | 400vac |
Frequency(Hz) | 50 ± 0.1%. |
Waveform | Pure Sine Wave |
THDv | THD < 3% |
Overload | 125% of rated load last for 60second,150% of rated load last for 1 second. |
Isolation Transformer | Inbuilt Isolation Transformer. |
Battery | |
Battery type | VRLA or SMF. |
Battery voltage | 240 vdc |
Charger current (Max) | 1~10 Amp Standard (Higher Rating optional) |
Recharge Time | < 10hours to 90% |
Other Features | |
Display | LCD display indicating (Input voltage ,Output voltage,Input frequency, Output frequency,load capacity,battery voltage) LED indications: Mains ,AC Mode,DC Mode,Low battery,Overload. |
Alarm | Battery low voltage, abnormal power supply, UPS failure,Overload. |
Protection | Protection for battery low voltage, overload, short circuit and over temprature. |
Noise (db) | <65 dB (1meter) |
Efficiency | >90% |
Temperature & RH | 0 ~ 40°C ,0 ~ 95%, No condensation |
Dimension (WxDxH)mm | 400x950x770 |
Weight (kg.) | 180 Kg |