Online UPS 3 Phase & 3 Phase O/P-PS 33 Series

Key Features & Application
- High frequency and double conversion on-line technology
- Advanced PFC technology, >0.99
- 3U frame, rack-mounted and tower convertible
- EPO function
- Wide input voltage range
- Fully digitized DSP control
- lnbullt Parallel redundancy
- Advanced battery management
- Lightning and surge protection, short circuit and
overload poteclion - Multilingual LCD and LED display
- EMIIRFI noise filter
- Smart RS232 communication with monitoring software
- Optional SNMP card slot
- Paralleling of rack upto 4
- lnbuilt granular power Paralleling
- Being output power factor is 1all KVA module are KW rated.
Model | PS 33 Series |
Three Phase input & Three phase Output | |
INPUT | 380/400/415Vac, (3Ph+N+PE) |
Nominal Voltage | 208~478 Vac |
Operating Voltage range | 40Hz – 70Hz |
Operating frequency range | >-0.99 |
Power factor | 2%(100% nonlinear load) |
Harmonic distortion (THDi) | |
Bypass voltage range | Max. voltage: 220V:+25%(optional + 10%,+15%+20%); 230V: +20%(optional+10%, 15%); 240V: +15%(optional+10%)Min . voltage: -45% (optional-20%, -30%) |
Bypass frequency range | Frequency protection range:+-10% |
Generator input | Support |
Overload | 125% : 1min, 150%: 200ms |
Output | |
Rated Voltage | 380/400/415 Vac, (3Ph + N + PE) |
Power factor | 1.0(6KVA=6KW, 10KVA=10KW,20KAV=20KW,30KVA=30KW,40KVA=40KW |
Voltage regulation | +-1% |
Output frequency | +1%/+2%/+4%/+5%/+10% of the rated frequency (Selectable) Mains Mode(50/60+-0.1%) Hz Free Running |
Isolation transformer | Available |
Creat factor | 3:1 |
Harmonic distortion (THDi) | <-2% with linear load,<-5% with non linear load |
Effciency | 96.0% |
BATTERY | |
Battery voltage | +-192V/+-204V/+-216V/+-228V+-240Vdc |
Charge Current (A) | 6A (Max) per module , (charge current can be set according to batery capacity insatted) |
SYSTEM FEATURES | |
Transfer time | Utility to Battery : 0ms; last 10min,<-150%:last 1min |
Overload | Load <110%:last 60min, <125% :last 10min, <150%:last 1min |
Short Circuit | Hold Whole System |
OverheatNoise suppression
Audible & visual alarms Status LED & LCD display Reading on the LCD display Communication interface ENVIRONMENTTAL Operating temperature Storage temperature Humidity range Altitude Noise level (from 1M distance) STANDARDS Safety EMC |
Line Mode : Switch to Bypass; Backup Mode : Sut down UPS Immediately
Complies with EN62040-2 Line Failure, Battery Low ,Overload,System Fault Line Mode , Bypass Mode, Battery Low, Battery Bad,overload & UPS fault Input,Output,Battery,command,setting,maintenance RS232,RS485,Parallel,Intelligent slot,Relay card (optional),Battery temperature sentor (optional) 0℃ ~40℃ -25℃~55℃ 0~95%(non condensing) <1500m <65dB upto 300 KVA,<73 dB above 300 KVA IEC/EN62040-1; IEC/EN60950-1 IEC/EN62040-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61000-4-6; IEC61000-4-8 |