Online UPS Single Phase O/P-DS1108B16

Key Features & Application
- High reliability design
- Strong protection for load
- Wide input range
- Optimization of high-performance battery
- Battery cold start function
- Comprehensive and reliable protection
- User friendly network management
Model | DS1108B16 |
Capacity (KVA) | 8K |
INPUT | |
Rated input voltage | 220/230Vac |
Operating voltage range | 165 ~ 275 |
Operating frequency range | 50/60Hz ± 5% |
OUTPUT | |
Rated output voltage | 220Vac±1% / 230Vac±1% |
Output frequency | 50/60Hz±0.5% |
Crest factor | 3:1 (max) |
Max. efficiency | >91% |
Overload | 125% : 1min, 150%: 200ms |
Power factor | 0.7 / 0.8 / 0.9 (Optional) |
THD | 2% (Linear load) |
BATTERY | |
Battery voltage | 192Vdc |
Battery Configuration | 7AH/12V X16Nos, inbuilt |
SYSTEM FEATURES | |
Transfer time | 0 ms ( AC mode→ Battery mode) |
Communication interface | RS232, SNMP, Dry contact (optional) |
ENVIRONMENTAL | |
Operating temperature | 0~40℃ |
Humidity range | 0~95% (non condensing) |
Noise level | <45dB (1m from surface) |
PHYSICAL | |
Dimension W×D×H (mm) | 230x580x750 |
Net weight (kg)(without Battery) | 63 |
STANDARDS | |
Safety | IEC/EN62040-1; IEC/EN60950-1 |
EMC | IEC/EN62040-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61000-4-6; IEC61000-4-8 |